ESIE15-08B
|
Part 2. Troubleshooting
3. Symptom based troubleshooting
19/07/16
Page 55
Daikin Altherma Monobloc CA
3.5. Inaccurate temperature control (for both domestic hot water and space heating
operation)
Displayed date/time is
wrong - schedules not cor-
rectly executed.
Daylight Saving Time not
set correctly.
Check Daylight Saving Time settings.
Set Daylight Saving Time
according to operation
manual.
Incorrect setting of unit
control method (setting
[C-07]).
Incorrect setting of unit
control method (setting
[C-07]) (leaving water con-
trol, room thermostat con-
trol, ext. room thermostat
control).
Check if setting [C-07] (leaving water con-
trol, room thermostat control, ext. room
thermostat control) is in set according to
the application.
Incorrect setting of user
interface location (user
menu [A.2.1.B]).
Incorrect setting of user
interface location (user
menu [A.2.1.B]) (at unit/in
room).
Check if setting of user interface location
(user menu [A.2.1.B]) (at unit/in room) is
set correctly.
Incorrect setting of space
heating OFF temperature
(setting [4-02]).
Incorrect setting of space
heating OFF temperature
(setting [4-02]).
Check if setting space heating OFF tem-
perature (setting [4-02]) is correct (keep at
35°C).
Preferential kWh rate
power supply settings and
electrical connections do
not match.
Preferential kWh rate
power supply settings and
electrical connections do
not match.
Check preferential kWh rate power supply
settings and electrical connections (see
installer reference guide).
Root cause category: component - electrical
Hydro PCB A1P not opera-
tional.
•
No power supply.
• Faulty
transformer
TR1.
• PCB
malfunction.
•
Confirm if a small green led is blinking
in regular intervals.
•
Confirm power supply towards PCB
A1P.
•
Check good operation of transformer
TR1.
• Re-establish
power
to
PCB.
Replace Hydro PCB A1P
in case power supply and
transformer TR1 are OK
but led is not blinking.
Reactor coil
(L1R/L2R/L3R) broken.
Component problem.
Check continuity of the reactor coil.
Replace the reactor coil in
case faulty.
Root cause category: hardware
Cooling/heating operation
starts, but stops immedi-
ately.
• Refrigerant
overcharge.
•
Mixing of air in
refrigerant system.
Check refrigerant.
After vacuum drying,
charge correct amount of
refrigerant.
Possible failures
Root cause
Check
Corrective action
Root cause category: parameter (setting)
Incorrect setting of unit control
method (setting [C-07]).
Incorrect setting of unit control
method (setting [C-07]) (leav-
ing water control, room ther-
mostat control, ext. room
thermostat control).
Check if setting [C-07] (leaving
water control, room thermostat
control, ext. room thermostat
control) is in set according to
the application.
Adjust setting to match appli-
cation.
Incorrect setting of user inter-
face location (user menu
[A.2.1.B]).
Incorrect setting of user inter-
face location (user menu
[A.2.1.B]) (at unit/in room).
Check if setting of user inter-
face location (user menu
[A.2.1.B]) (at unit/in room) is
set correctly.
Adjust setting to match appli-
cation.
Incorrect setting of pump oper-
ation mode (continuous, sam-
ple, request) (setting [F-0D]).
Incorrect setting.
Confirm setting [F-0].
Adjust setting [F-0] if required.
(Factory setting: [F-0]=1).
Possible failures
Root cause
Check
Corrective action