ESIE15-08B
|
Part 4. Maintenance
2. Maintenance procedures
Page 136
19/07/16
Daikin Altherma Monobloc CA
2.3. Checking the pressure relief valve of Space Heating circuit
2.4. Checking the relief valve of the Domestic Hot Water tank - field supply
2.5. Checking the filters of Space Heating circuit
Actions
Remarks
Open the valve and check the correct operation:
•
If the fluid flow is high, no blockage is suspected.
•
If the fluid flow is low or contains debris or dirt:
•
Open the valve until fluid is without dirt.
•
Flush the system and install an additional water filter.
A magnetic cyclone filter is to be preferred.
Make sure to check the water pressure again after this check as
it might have dropped. When below 1 bar, add fluid.
Do not exceed 2 bar.
W
ARNING
Discharged fluid may be very hot!
Actions
Remarks
Open the valve and check the correct operation:
•
If the fluid flow is high, no blockage is suspected.
•
If the fluid flow is low or contains debris or dirt:
•
Open the valve until fluid is without dirt.
•
Flush and clean the tank and piping between relief valve
and cold water inlet.
Make sure that all taps and air vent are open, otherwise the tank
might be sucked vacuum and the water will not move.
W
ARNING
Discharged fluid may be very hot!
Actions
Remarks
Check water filters and clean when required.