Part 2. Troubleshooting
5. Component checklist - Refrigerant Circuit
Page 88
19/07/16
Daikin Altherma Monobloc CA
5. Component checklist - Refrigerant Circuit
5.1. Required tools for component check
Figure 2 - Required tools for component check
Overview of component checklists:
5.2. Thermistors
1. Magnet (tool part N° 9950038)
3. D-checker (tool part N° 999495P)
2. Inverter analyzer (tool part N° 1368521)
I
NFORMATION
The D-checker requires software and a driver.
Software for D-checker: Extranet/Software downloads/D-checker
Driver for D-checker: Extranet/Software downloads/Heating products/USB driver
Thermistors..................................................................................... 88
Compressor M1C ........................................................................... 91
Muffler............................................................................................. 93
Pressure sensor S1NPH ................................................................ 94
High pressure switch S1PH............................................................ 96
Electronic expansion valve Y1E .....................................................97
4-way valve Y1R.............................................................................99
Inverter PCB2 ...............................................................................101
Fan motor .....................................................................................103
Technical specification
Description
A single type of thermistor is used; the resistance vs. temperature characteris-
tics shown in Table 2-4 on page 90.
The thermistors are used to measure the temper-
ature at multiple locations inside the Daikin
Altherma
Monobloc CA
. The measured tempera-
tures are processed by the PCB1 Main board.
Location
Wiring diagram
PCB1
Unit
1
2
3