Part 2. Troubleshooting
4. Component checklist - Water Circuit
19/07/16
Page 75
Daikin Altherma Monobloc CA
4.5. Water pump M2P (DHW pump)
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
3.
Drain the water circuit, refer to Installer Reference Guide.
4.
Locate the pump in the piping installation.
5.
Remove the 4 screws that fix the pump motor to the pump house.
6.
Separate the pump motor from the pump house.
7.
Inspect the rotor and check that it rotates smoothly.
8.
After water pump assembly and filling the water circuit, check pump for leaks.
-
Replace the seal if the water pump leaks.
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
3.
Remove the front panel of the control box.
4.
Power the Daikin Altherma Monobloc CA.
5.
Check fuse FU1 on A1P, if blown, find cause and replace.
Technical specification
Description
DHW pump power consumption: 2A (inrush) - 1A (continuous) - 230 VAC
The water pump M2P circulates the water in the
DHW circuit.
Location
Wiring diagram
Switch box - Control box
Unit
Check procedure
Mechanical check
Electrical check
W
ARNING
: R
ISK
OF
F
IRE
•
When reconnecting a connector to the PCB, do not apply force or damage the connector or the connector pins on
the PCB.
X1M
X8M
X2M
K2A
K3M
K1A
A4P
F2B
X4M
Not applicable