ESIE15-08B
|
Part 4. Maintenance
1. Yearly maintenance intervals and procedures
19/07/16
Page 135
Daikin Altherma Monobloc CA
Part 4. Maintenance
1. Yearly maintenance intervals and procedures
Following items should be checked on the product at least once a year:
•
Fluid pressure of Space Heating circuit
•
Relief valve hose
•
Pressure relief valve of Space Heating circuit
•
Pressure relief valve of Domestic Hot Water tank
• Filters
•
Draining of the Domestic Hot Water tank
• Anode
•
Descaling and chemical disinfection
• Switch
box
•
Domestic hot water tank booster heater (in case non-integrated tank)
• Heat
exchangers
2. Maintenance procedures
The following procedures describe how to perform the maintenance on each items.
2.1. Checking fluid pressure of Space Heating circuit
2.2. Checking the pressure relief valve hose
W
ARNING
Before performing any maintenance, power off the unit.
I
NFORMATION
After all checks are made, make sure the water and brine circuits are filled properly again and fluid pressures are okay
(1 - 2 bar).
Actions
Remarks
Check if fluid pressure between 1 and 2 bar.
Manometer is located under grey flap on front panel.
If pressure < 1 bar, add fluid.
Do not add to over 2 bar.
Actions
Remarks
Check whether the pressure relief valve hose is positioned
appropriately to drain the water.