ESIE15-08B
|
Part 2. Troubleshooting
4. Component checklist - Water Circuit
19/07/16
Page 65
Daikin Altherma Monobloc CA
4. Component checklist - Water Circuit
Overview of component checklists:
4.1. Backup heater E1H, E2H, E3H
Not applicable
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
Backup heater E1H, E2H, E3H.......................................................65
Booster heater E4H ........................................................................69
Thermistors .....................................................................................70
Water pump M1P (Main Supply Pump) ..........................................73
Water pump M2P (DHW pump) ......................................................75
Plate type heat exchanger ............................................................. 77
Thermal protector backup heater Q1L ........................................... 79
Water flow sensor B1L ................................................................... 81
3-way valve M3S............................................................................ 84
Extension PCB A4P ....................................................................... 86
Technical specification
Description
The 2-stage backup heater is composed of heater E1H (3 x 1 kW) and E2H (3 x 2
kW) or E3H (1 x 3 kW).
The backup heater is used to assist the heat pump
system to heat the water for space heating and
domestic hot water operation.
Location
Wiring diagram BUH*3V
Switch box - BUH*3V Kit
Unit BUH*3V
Wiring diagram BUH*9V
Switch box - BUH*9V
Unit BUH*9V
Check procedure
Mechanical check
Preliminary check
X15M
K2R
X14M
K2M
Q1L
K1M
K5M
K1R
F1B
X15M
K2R
X14M
K2M
Q1L
K1M
K5M
K1R
F1B