ESIE15-08B
|
Part 2. Troubleshooting
5. Component checklist - Refrigerant Circuit
Page 102
19/07/16
Daikin Altherma Monobloc CA
10. Disconnect the compressor wires and connect the compressor wires to the Inverter Analyzer (SPP number 1368521).
11. Power the Daikin Altherma Monobloc CA.
12. Locate SW1 on the PCB3 service.
13. Press SW1 for 5 seconds to activate the inverter test.
14. Check that all LEDs on the Inverter Analyzer are lit; if not, replace the inverter board, refer to
15. Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
16. Wait a few minutes and confirm that the LED's on the inverter analyzer are off.
17. Disconnect the inverter analyzer from the U V W wiring.
18. Re-connect the U V W leads to the compressor.
W
ARNING
Electrical shock hazard. Do not touch life wires.
C
AUTION
When wiring the compressor, observe UV W as indicated on the compressor.