ESIE15-08B
|
Part 2. Troubleshooting
5. Component checklist - Refrigerant Circuit
19/07/16
Page 103
Daikin Altherma Monobloc CA
5.10. Fan motor
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
3.
Remove the hydrobox top plate assembly, refer to
"Removing the hydrobox top plate assembly" on page 110
4.
Remove the hydrobox front plate, refer to
"Removing the hydrobox front plate" on page 111
5.
Remove the top plate, refer to
"Removing the top plate" on page 112
.
6.
Remove the front plate assembly, refer to
"Removing the front plate assembly" on page 113
7.
Check the state of the propeller, replace the propeller if damaged, deformed, cracked or broken, refer to
propeller fan blade assembly" on page 115
8.
Check the motor friction, only perform electrical check if motor runs with low friction. Replace fan motor if friction is abnormal,
refer to
"Replacing the DC fan motor assembly" on page 116
General
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
3.
Remove the top plate, refer to
"Removing the top plate" on page 112
.
4.
Remove the front plate assembly, refer to
"Removing the front plate assembly" on page 113
Technical specification
Description
The motor has a single connector for DC power and the rotation counter feed
back from the integrated pulse generator (4 pulses/revolution).
The fan motor runs on a fixed speed to supply the
required air flow rate.
Location
Wiring diagram
PCB2
Unit
Check procedure
Mechanical check
Electrical check
W
ARNING
: R
ISK
OF
F
IRE
•
When reconnecting a connector to the PCB, do not apply force or damage the connector or the connector pins on
the PCB.