
ESIE15-08B
|
Part 2. Troubleshooting
2. Error code based troubleshooting
19/07/16
Page 47
Daikin Altherma Monobloc CA
2.63. “89-01” – Plate heat exchanger freeze-up error
2.64. “89-02” – Plate heat exchanger freeze-up warning during space heating / DHW
production
Trigger
Effect
Reset
When warning 89-02 (Tc < 0°C during
space heating) occurs 3 times (with less
than 30 minutes between each abnormal-
ity).
Unit stops operating.
Manual reset via user interface.
When warning 89-03 (Te < x°C during
defrost) occurs 3 times (with less than 30
minutes between each abnormality).
Unit stops operating.
Manual reset via user interface.
Possible cause
Check
Corrective action
Faulty heat exchanger thermistor R2T.
Check hydrobox heat exchanger thermis-
tor R2T (see page 70).
Replace heat exchanger thermistor when
required (see page 124).
Faulty hydro PCB A1P.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if hydro PCB A1P receives power.
Adjust the power to the PCB.
Replace hydro PCB A1P when alive led is
not blinking in regular intervals.
Adjust software of hydro PCB A1P or
install correct spare part when required.
Refrigerant shortage.
Check for refrigerant shortage (see
page 106).
Perform leak test.
If charge is lower than indicated on name-
plate, check for leaks and recharge unit
with correct amount of refrigerant.
Water pressure is too low
Check the water pressure on the pressure
gauge.
Increase water pressure till ~2 bar. Refer
to the Installer Reference Guide.
Check for possible water leaks.
Water flow is too low.
Check the minimum water flow required
for the system. Refer to Installer Refer-
ence Guide.
Adjust system to meet the water flow
requirements.
Water volume is too low.
Check if the smallest water volume meets
the requirements. Refer to "Installer Ref-
erence Guide". (Pay attention to the
by-pass in the water circuit!)
Adjust system and water volume to the
requirements as described in the Installer
Reference Guide.
Trigger
Effect
Reset
Tc is below 0°C during space heating.
Unit will continue operation.
Auto-reset when problem is solved.
Warning might result to 89-01 error if it
occurs 3 times.
R3T (liquid refrigerant) < or = 0°C during
space heating or DHW.
Unit will stop and restart when problem is
solved.
Possible cause
Check
Corrective action
Faulty 4-way valve.
Check 4-way valve (see page 99).
Replace 4-way valve when required (see
page 127).