ESIE15-08B
|
Part 2. Troubleshooting
4. Component checklist - Water Circuit
19/07/16
Page 81
Daikin Altherma Monobloc CA
4.8. Water flow sensor B1L
1.
Power the Daikin Altherma Monobloc CA.
2.
Activate “Installer level” on the user interface, refer to “Installer Level Settings” in the Installer Reference Guide to access the
most used commands.
3.
On the user interface, select Actuator test run A.7.4.
4.
On the user interface, activate the water pump (A.7.4.6).
5.
On the user interface, select Flow Rate 6.1.8.
6.
The displayed flow rate must be between 5 and 40 l/minute.
Technical specification
Description
The water flow sensor output signal versus flow is shown in the graph below.
The water flow sensor measures the flow in the
water circuit.
Location
Piping diagram
Switch box
Unit
Check procedure
Electrical check
W
ARNING
: R
ISK
OF
F
IRE
•
When reconnecting a connector to the PCB, do not apply force or damage the connector or the connector pins on
the PCB.
I
NFORMATION
The flow sensor B1L connector must be plugged into X4A on PCB A1P.
TR1
X5M
X4M
A2P
X3M
X7M
A1P
PCB3
X6Y
X45A