ESIE15-08B
|
Part 2. Troubleshooting
5. Component checklist - Refrigerant Circuit
19/07/16
Page 91
Daikin Altherma Monobloc CA
5.3. Compressor M1C
1.
Check if the unit is grounded.
2.
Check if the stop valve is open.
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
3.
Remove the top plate, refer to
"Removing the top plate" on page 112
.
4.
Remove the front plate assembly, refer to
"Removing the front plate assembly" on page 113
5.
Open the compressor insulation.
6.
Check the condition of the compressor dampers and piping.
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
3.
Remove the hydrobox top plate assembly, refer to
"Removing the hydrobox top plate assembly" on page 110
4.
Remove the hydrobox front plate, refer to
"Removing the hydrobox front plate" on page 111
5.
Remove the top plate, refer to
"Removing the top plate" on page 112
.
Technical specification
Description
Compressor name: 2YC63PXD#C.
Type: inverter driven, double swing.
The compressor M1C compresses the refrigerant
in the refrigerant circuit.
Location
Piping diagram
Unit
Check procedure
Preliminary check
Mechanical check
Electrical check
W
ARNING
: R
ISK
OF
F
IRE
•
When reconnecting a connector to the PCB, do not apply force or damage the connector or the connector pins on
the PCB.