ESIE15-08B
|
Part 3. Repair
2. Unit specific repair procedures Monobloc CA
19/07/16
Page 119
Daikin Altherma Monobloc CA
Installation
1.
Proceed in reverse order.
2.2.4. Replacing the PCB1 main
2.2.4.1 Preliminary actions
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
3.
Remove the switch box, refer to
"Replacing the switch box" on page 117
2.2.4.2 Procedure
Removal
1.
Unlock the 4 latches (1) and remove the electrical component box cover (2) from the electrical component box (3).
2.
Loosen and remove the 2 screws (4) that fix the PCB assembly main (5).
3.
Loosen and remove the screw (6) that fixes ground wires E1, E2 (7).
I
NFORMATION
Replace all tie wraps that were cut during removal.
W
ARNING
: R
ISK
OF
F
IRE
•
When reconnecting a connector to the PCB, do not apply force or damage the connector or the connector pins on
the PCB.