ESIE15-08B
|
Part 2. Troubleshooting
5. Component checklist - Refrigerant Circuit
Page 94
19/07/16
Daikin Altherma Monobloc CA
5.5. Pressure sensor S1NPH
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
3.
Remove the hydrobox top plate assembly, refer to
"Removing the hydrobox top plate assembly" on page 110
4.
Remove the hydrobox front plate, refer to
"Removing the hydrobox front plate" on page 111
.
5.
Remove the top plate, refer to
"Removing the top plate" on page 112
6.
Remove the front plate assembly, refer to
"Removing the front plate assembly" on page 113
.
7.
Open the compressor insulation.
8.
Connect a pressure gauge to the high pressure service port and read the pressure.
9.
From the graph below, determine the expected sensor output signal.
Technical specification
Description
The pressure sensor S1NPH is an analog pressure sensor.
The pressure sensor S1NPH measures the pres-
sure in the high pressure section of the refrigerant
circuit.
Location
Piping diagram
PCB1
Unit
Check procedure
Electrical check
W
ARNING
: R
ISK
OF
F
IRE
•
When reconnecting a connector to the PCB, do not apply force or damage the connector or the connector pins on
the PCB.