ESIE15-08B
|
Part 2. Troubleshooting
2. Error code based troubleshooting
Page 42
19/07/16
Daikin Altherma Monobloc CA
2.51. “U3-00” – Abnormal stop of underfloor heating dry-out scheduled operation
2.52. “U4-00” – Defective indoor-outdoor transmission
Trigger
Effect
Reset
Screed dry-out program was interrupted.
Unit will stop UFH dry-out schedule.
Manual reset via user interface -> only
possible in "installer" level.
Possible cause
Check
Corrective action
User interface has been turned off.
Check user interface.
Restart screed dry out program. Refer to
the Installer Reference Guide.
Faulty or disturbance of the power supply.
(Imbalance > 10%) Power drop.
Short circuit.
Check if the power supply is conform with
regulations. No fluctuations in frequency.
Adjust power supply when required.
Power reset via outdoor unit.
No heat source detected.
Check backup heater.
Restart screed dry out program. Refer to
the Installer Reference Guide.
Trigger
Effect
Reset
Hydro PCB A1P detects abnormal trans-
mission to outdoor main PCB for a certain
time.
Unit will stop operation.
Auto-reset.
Possible cause
Check
Corrective action
Power supply is not OK -> imbalance
> 10%.
Check power supply for voltage fluctua-
tions (> 10%).
Voltage fluctuations should be less than
10%.
Wiring between outdoor main PCB and
hydro PCB A1P is not OK.
Check the wiring (refer to the wiring dia-
gram).
Correct the wiring.
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when alive led
is not blinking in regular intervals (see
page 119).
Faulty hydro PCB A1P.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if hydro PCB A1P receives power.
Adjust the power to the PCB.
Replace hydro PCB A1P when alive led is
not blinking in regular intervals.
Adjust software of hydro PCB A1P or
install correct spare part when required.
External factor (e.g. electrical noise)
(cause when error is reset after power
reset, and error happens again after
awhile).
Check for source which could cause elec-
trical interference.