ESIE15-08B
|
Part 3. Repair
2. Unit specific repair procedures Monobloc CA
Page 124
19/07/16
Daikin Altherma Monobloc CA
2.2.6. Replacing a thermistor
2.2.6.1 Preliminary actions
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
3.
Remove the front panel, refer to
"Removing the front plate assembly" on page 113
2.2.6.2 Procedure
The position of the thermistors is illustrated in
"Components overview" on page 154
Figure 16 - Thermistor location
W
ARNING
: R
ISK
OF
F
IRE
•
When reconnecting a connector to the PCB, do not apply force or damage the connector or the connector pins on
the PCB.
1. R1T
3. R3T
2. R2T
Thermistor
Processed
on PCB
Connector: pin
Access Information
R1T (discharge)
PCB1
S90: 5-6
Remove compressor sound insulation (top).
R2T (heat exchanger)
PCB1
S90: 3-4
-
R3T (air)
PCB1
S90: 1-2
-
3
1
2