Part 2. Troubleshooting
2. Error code based troubleshooting
Page 26
19/07/16
Daikin Altherma Monobloc CA
2.16. “E3-00” – High pressure abnormality (refrigerant)
2.17. “E4-00” – Actuation of sensor (low pressure)
External factor (e.g. electrical noise)
(cause when error is reset after power
reset, and error happens again after
awhile).
Check for source which could cause elec-
trical interference.
Faulty fan motor.
Check fan motor (see page 103)
Check fan motor connection and wiring.
Replace fan motor when required (see
page 116). Adjust wiring when required.
Faulty or disturbance of the power supply.
(Imbalance > 10%) Power drop.
Short circuit.
Check if the power supply is conform with
regulations. No fluctuations in frequency.
Adjust power supply when required.
Power reset via outdoor unit.
Trigger
Effect
Reset
1. High pressure switch opens due to
pressure > 41,7 bar.
2. High pressure control (HP > 38 bar)
occurs 16 times within 300 minutes.
Unit will stop operating.
Manual reset via user interface.
Possible cause
Check
Corrective action
Refrigerant overcharge.
Check for refrigerant overcharge.
Charge the correct refrigerant amount
when required.
Humidity in refrigerant (ice formation in
expansion valve).
Check for humidity in the refrigerant.
In case of suspicion of humidity, recover
vacuum and recharge with virgin refriger-
ant.
Non condensables in refrigerant.
Check for non condensables in refriger-
ant.
In case of suspicion of non condensables
recover, vacuum and recharge with virgin
refrigerant.
Refrigerant circuit is clogged.
Check for possible blockage (blockages
can be checked by measuring the refriger-
ant/pipe temperature. Sudden drop in
temperature could indicate a blockage
(remark: this is not valid for the expansion
valve).
Replace the blocked part.
Faulty pressure sensor.
Check pressure sensor (see page 94).
Replace the pressure sensor when
required (see page 130).
Faulty high pressure switch.
Check high pressure switch (see
page 96).
Replace the high pressure switch when
required (see page 129).
Stop valve is closed.
Check if stop valve is open.
Open stop valve when required.
Faulty fan motor.
Check fan motor (see page 103)
Check fan motor connection and wiring.
Replace fan motor when required (see
page 116). Adjust wiring when required.
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when alive led
is not blinking in regular intervals (see
page 119).
Trigger
Effect
Reset
When refrigerant pressure is below 1.2
bar for 5 minutes.
Unit will stop operating.
Manual reset via user interface.
Possible cause
Check
Corrective action
Stop valve is closed.
Check if stop valve is open.
Open stop valve when required.