Calculating the Calibration Values
Valve Cal 2
Note:
If the dual loop control feature is enabled, the valve cal 2 value will be replaced by the Sgain
(pressure system gain) value.
When a fast close valve is selected, the valve cal 2 value is utilized to enable a high resolution rate control for
lower application rates.
Enter a non-zero value for the time, in milliseconds, which the valve will be fully opened before switching into
high resolution control. For example, a value of 200 will give the valve a 200 millisecond “burst” at a full 12V to
open the fast valve from the closed position before resuming product rate control. A zero value will disable this
feature.
Flow Cal (Dual Loop Control Mode)
The flow cal value has two components which may be used to adjust the response of the application system.
Note:
It is recommended to set the Sgain value prior to making any adjustments to the flow cal value.
Flow System Gain.
The first digit(s) of the flow cal correspond to a flow system gain between 1 and 99. The
higher the flow system gain, the more aggressive the system will respond to changes in flow rate.
Note:
When entering a flow gain value from 1 to 9, it is not necessary to enter a zero in front of the value.
If the system adjusts to rate control changes too slowly, increase the flow gain digit(s) to increase the system
response rate. If the system overshoots or oscillates around the desired flow rate, decrease the flow gain
digit(s) to help stabilize the system.
Dead Band Digit.
The last, or right most, digit in the flow cal value is the dead band digit. The dead band digit
is the allowable difference between the target rate and the actual application rate. The values range from 1 to
9, where 1 equals 1% difference and 9 equals 9% of the difference.
Sgain (Pressure System Gain - Dual Loop Control Mode)
The default setting for the Sgain value is 100. To adjust the system aggressiveness, enter a value between 1
and 999 as necessary.
Note:
It is recommended to increase or decrease the current value in increments of 10 or less when
making adjustments to the Sgain setting. If the new value does not produce significant or notable
changes in the system response, increments of 20 may be used.
Increase the Sgain value if the observed product pressure increases too slowly or if the system takes a long
time to reach a set standby pressure or rate input change. If the system is consistently over shooting a set
standby pressure or oscillating around a target rate, decrease the Sgain value until the system stabilizes.
Flow System Gain
Dead Band
Percentage
103
Содержание Envizio Pro
Страница 3: ......
Страница 13: ...Table of Contents x Envizio Pro and Envizio Pro II Installation and Operation Manual ...
Страница 32: ...3 P N 016 0171 493 Rev I 17 Installation FIGURE 1 Envizio Pro Kit Contents Drawing Number 054 2040 004 ...
Страница 51: ...Chapter 4 36 Envizio Pro and Envizio Pro II Installation and Operation Manual ...
Страница 65: ...Chapter 5 50 Envizio Pro and Envizio Pro II Installation and Operation Manual ...
Страница 193: ...Chapter 9 178 Envizio Pro and Envizio Pro II Installation and Operation Manual ...
Страница 197: ...Chapter 10 182 Envizio Pro and Envizio Pro II Installation and Operation Manual ...
Страница 229: ...Appendix D 214 Envizio Pro and Envizio Pro II Installation and Operation Manual ...
Страница 285: ...Index 270 Envizio Pro and Envizio Pro II Installation and Operation Manual ...