16.3.1.2
Restarting or stopping the communication
A restart of communication is required after changes of the interface configuration (e. g. sta-
tion address and IP configuration) in order that the changed settings become effective with-
out switching the mains.
Station name and IP configuration
For restarting the communication, there are two options:
•
= 1 (restart with current values).
•
must be set = 2 (restart with the values saved last).
The following option can be used to stop communication:
•
must be set = 5 (stop network communication).
Parameter
Address
Name / setting range / [default setting]
Info
0x2380
PROFINET communication
Restart / stop communication
•
When the device command has been executed successfully, the value
0 is shown.
0 No action/no error
Only status feedback
1 Restart with current values
Restart communication with the current values.
2 Restart with default values
Restart communication with the values of the PROFINET parameters that
have been saved last (0x2381:001 ... 0x2381:009).
5 Stop network communication
Stop communication
10 In process
Only status feedback
11 Action cancelled
12 Fault
16.3.1.3
Settings in the Siemens »TIA Portal«
Here, commissioning with the Siemens »TIA Portal« is described. Please note
that in the standard setting of the Siemens »TIA Portal« changes of network
parameters carried out by a Lenze engineering tool (e. g. »EASY Starter«) may
be overwritten.
1. Go to the device configuration and open the "net view" to drag the inverter from the cata-
log to the net view of the PROFINET.
2. Assign the inverter to the associated IO-Controller.
3. Mark the inverter and change to the "device view".
4. Set the IP address and the station name ("PROFINET device name") in "Properties".
Station name and IP configuration
In order that the inverter can be identified via Ethernet when the IO controller is
switched off, the station name and the IP configuration must be saved in the
inverter with mains failure protection via the separate entry with the »EASY
Starter«.
See:
5. Below the device name and the name of the device description file, the device view shows
the pre-assignment of output and input process data words.
In slot 1, pre-assigned process data words can be changed.
When using PROFIsafe, you can add safety process data in slot 2.
6. Save the project in the engineering tool.
7. Load the configuration into the IO-Controller.
8. Set the IO-Controller to "RUN".
Configuring the network
PROFINET
Commissioning
356
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......