13.4.8
Set oscillation damping
The oscillation damping serves to reduce the oscillations during no-load operation which are
caused by energy oscillating between the mechanical system (mass inertia) and the electrical
system (DC bus). Furthermore, the oscillation damping can also be used to compensate for
resonances.
Damping is possible only for constant oscillations at a steady-state operating
point.
Oscillations occurring sporadically cannot be damped.
Oscillation damping is not suitable for oscillations occurring during dynamic pro-
cesses (e.g. accelerations or load changes). Oscillation damping is only active if
the setpoint speed is greater than 10 rpm and the DC-bus voltage exceeds a
value of 100 V.
The determination of the oscillation is based on the active current. In order to obtain the
alternating component of the active current, this current is differentiated. This signal is then
passed through a PT1 filter.
0x2B0A:002
0x2B0A:001
0x2B0A:004
0x2B0A:002
0x2DD1:002
Zeitkonstante
Verstärkung
Rampen-Endfrequenz
Begrenzung
Istwert Wirkstrom
Sollwert
Drehfrequenz
Pendeldämpfung
Identification of the oscillation
Before the oscillation damping can be parameterised, the oscillation must be identified. One
option is to look at the motor current when the oscillation damping is switched off (gain = 0
%). The oscilloscope function of the »PLC Designer« enables to record the following currents:
•
Q current
•
Total current
A passive load and continuous operation with constant speed (steady-state operation) result
in a constant current. If the drive oscillates, the motor current oscillates as well. This makes it
possible to detect the frequency and amplitude of the oscillation by means of the AC compo-
nent in the motor current. Hereinafter this AC component will be referred to as "current oscil-
lation".
Parameter setting
The gain of the oscillation damping is to be set according to the following equation:
=
×
×
Stromamplitude
Verstärkung der Schwingungsdämpfung
100%
2 Gerätemaximalstrom
The time constant must be set so that the oscillation can be dampened, but that higher-fre-
quency components are filtered from the signal. The time constant is determined from the
reciprocal value of the double current oscillation frequency:
=
×
1
Zeitkonstante
2 Schwingfrequenz
The calculated oscillation frequency can be limited before being added to the rotating field
frequency. The maximum frequency can be derived from the amplitude of the current oscilla-
tion, the rated motor current and the slip frequency of the connected motor:
×
=
×
-
2 Amplitude der Stromschwingung
max. Frequenz
Nennschlupffrequenz
Motor Bemessungsstrom
Configuring the motor control
V/f characteristic control for asynchronous motor (VFC open loop)
Set oscillation damping
247
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......