The distance between the touch probe sensor and the position where the tool starts is
assigned via the Tool sensor distance parameter.
The "mark stack" function is automatically activated when the Tool sensor distance parameter
is greater than der Cycle length parameter.
Parameter
•
Tool sensor distance
•
After a mark has been detected, the value of the mark deviation is released for correction only
if the position in the register cycle has covered the distance of the mark register.
Parameter
Address
Name / setting range / [default setting]
Info
0x500A:031
Cycle length
0.0001 ... [360.0000] ... 214748.3647
•
Setting can only be changed if the inverter is inhibi-
ted.
The cycle length for an unlimited traversing range defines the position
where the measuring system is repeated (position return to 0).
0x5041:015
Mark window teaching
0 Master value correction
1 Tool correction
0x5041:120
Activate tool correction
false FALSE
true TRUE
0x5041:121
Tool sensor distance
0.0000 ... [360.0000] ... 214748.3647
0x5041:126
Tool mark window size
0.0000 ... [40.0000] ... 214748.3647
0x5041:127
Tool mark window offset
0.0000 ... [0.0000] ... 214748.3647
0x5041:129
Activate tool mark window
false Deactivated
true Activated
0x5042:140
Tool sensor set position
•
Read only
7.9.2
Mark failure detection
If the output is set via bit 23 in the Status signals parameter, no mark was detected within the
configured mark window.
Bit 23
In this case, an ideal virtual mark for the system is created. Subsequent functions can continue
to be executed.
The maximum number of mark failures is set via the Max. number of missed marks (tool)
parameter. If no mark is detected within the mark window, an internal counter is incremented.
If the number of failed marks reaches the limit set in the Max. number of missed marks (tool)
parameter, a corresponding error is output at the error output of the technology application.
Parameter
Address
Name / setting range / [default setting]
Info
0x5041:128
Max. number of missed marks (tool)
0 ... [20] ... 4294967295
Configuring the "Sync and Correction" TA
Tool correction
Mark failure detection
145
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......