16.2.1
Commissioning
During commissioning, the EtherCAT master operates as gateway to access from the Engineer-
ing PC to the slaves.
In the following, the required steps are described to control the device as EtherCAT slave.
Preconditions
•
The inverter is networked as EtherCAT slave to an EtherCAT master and, if necessary, fur-
ther EtherCAT devices.
See "Typical topologies" under:
•
The entire wiring has already been checked for completeness, short circuit and earth fault.
•
All EtherCAT devices are supplied with voltage and are switched on.
•
An Engineering PC with installed »PLC Designer« is connected to the master.
•
•
A »PLC Designer« project with current device description files for EtherCAT is available.
•
Download XML/ESI files for Lenze devices
•
The files are installed via the device repository of the »PLC Designer« (menu command
"Tools
à
Device repository").
Configuring the network
EtherCAT
Commissioning
335