Master-slave coupling
In the event of an active master/slave coupling (e. g. synchronism or cam profiler application),
the speed is not reduced automatically in the default setting. The automatic speed reduction
is generally realised via the master axis.
Automatic speed reduction is activated via the Follower - Response to SLS parameter.
If automatic speed reduction is activated, the cyclically specified setpoint values are reduced
to the limited speed. The synchronism of the master axis is no longer guaranteed.
An offset occurring between master and slave is automatically resolved by deactivating the
parameter.
An excessive rotational speed due to following error compensation is avoided by limiting the
setpoint values at the speed regulator input.
Parameter
Address
Name / setting range / [default setting]
Info
0x500A:150
SLS1
0.0000 ... [0.0000] ... 214748.3647
0x500A:151
SLS1 - deceleration time
0.000 ... [0.000] ... 2147483.647 s
0x500A:152
SLS2
0.0000 ... [0.0000] ... 214748.3647
0x500A:153
SLS2 - deceleration time
0.000 ... [0.000] ... 2147483.647 s
0x500A:154
SLS3
0.0000 ... [0.0000] ... 214748.3647
0x500A:155
SLS3 - deceleration time
0.000 ... [0.000] ... 2147483.647 s
0x500A:156
SLS4
0.0000 ... [0.0000] ... 214748.3647
0x500A:157
SLS4 - deceleration time
0.000 ... [0.000] ... 2147483.647 s
0x500A:159
Compensation velocity of SLS
0.0000 ... [0.0000] ... 214748.3647
0x500A:160
Follower - Response to SLS
false Inactive
true Active
0x500A:161
Speed controller limitation (SLS)
false Inactive
true Active
0x500A:162
Deactivate safety functions
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
Bit 1 Ignore SS1 request
Bit 2 Ignore SS2 request
Bit 3 Ignore SLS1-4 request
Bit 4 Ignore SDI request
0x500A:163
Limiter status
•
Read only
Bit 0 STO active
Bit 1 SS1 active
Bit 2 SS2 active
Bit 4 SLS1 active
Bit 5 SLS2 active
Bit 6 SLS3 active
Bit 7 SLS4 active
Bit 8 SDIpos active
Bit 9 SDIneg active
Technology application (TA) basic settings
Motion settings
Limitations
77
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......