9.3
Process input data (CiA 402 objects)
Parameter
Address
Name / setting range / [default setting]
Info
0x2830
Inverter control word
0x0000 ... [0x0000] ... 0xFFFF
The control word serves to influence the control functions.
Bit 0 Flying restart completed
This bit enables the control to report the acceptance of the recorded
speed to the "flying restart" function. Thus, the flying restart process is
completed.
Bit 1 Block flying restart
TRUE: the flying restart process is blocked.
Bit 4 Set load value
TRUE: set load value.
Bit 5 Select new actual position
TRUE: define new actual position.
•
Setting/shifting of Position actual value (
) to Actual position
start value (
) considering the set resolution (
).
•
Mode for setting the actual position:
Bit 6 Activate DC-injection braking or short-circuit
braking
DC-injection braking or short-circuit braking is activated via this bit.
Bit 10 Reserved
Bit 11 Reserved
0x2902
I component load value
-1000.0 ... [0.0] ... 1000.0 %
Setting of the load value.
0x6040
CiA: Controlword
0x0000 ... [0x0000] ... 0xFFFF
Mappable CiA 402 control word with bit assignment according to device
profile CiA 402.
Bit 0 Switch on
1 = switch-on
Bit 1 Enable voltage
1 = DC bus: Establish readiness for operation
Bit 2 Quick stop
0 = activate quick stop
Bit 3 Enable operation
1 = enable operation
Bit 4 Operation mode specific
Bit 5 Operation mode specific
Bit 6 Operation mode specific
Bit 7 Fault reset
0-1 edge = reset error
Bit 8 Halt
1 = stop motor (ramping down to frequency setpoint 0 Hz)
Bit 9 Operation mode specific
Operating mode dependent
Bit 14 Release holding brake
1 = releasing holding brake manually
CAUTION!
•
The manually triggered "Release holding brake" command has a direct
impact on the "Release holding brake [115]" trigger. Thus, the holding
brake can be manually released if the power section is switched off.
•
The responsibility for a manual release of the holding brake has the
external trigger source for the "Release holding brake" command.
0x6060
Modes of operation
Selection of the operating mode.
0 No mode change/no mode assigned
No operating mode (standstill)
2 CiA: Velocity mode
CiA 402 velocity mode
Operating mode "CiA 402 Velocity mode (vl)"
8 Cyclic sync position mode
Operating mode "CiA 402 Cyclic sync position mode (csp)"
9 Cyclic sync velocity mode
Operating mode "CiA 402 Cyclic sync velocity mode (csv)"
10 Cyclic sync torque mode
Operating mode "CiA 402 Cyclic sync torque mode (cst)"
0x607A
Target position
-2147483648 ... [0] ... 2147483647 pos. unit
Setting of the position setpoint.
0x60B1
Velocity offset
-480000.00 ... [0.00] ... 480000.00 rpm
Additive value for setpoint velocity or velocity feedforward control.
0x60B2
Torque offset
-3276.8 ... [0.0] ... 3276.7 %
Additive value for setpoint torque or torque feedforward control
•
100 % ≡ rated motor power (
)
0x60E0
Positive torque limit
0.0 ... [100.0] ... 3276.7 %
Positive torque limit source for speed control with torque limitation.
•
100 % ≡ Rated Motor Torque.
0x60E1
Negative torque limit
0.0 ... [100.0] ... 3276.7 %
Code previously C3687.
Negative torque limit source for speed control with torque limitation.
•
100 % ≡ Rated Motor Torque
Configure position control
Process input data (CiA 402 objects)
162
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......