Address
Name / setting range / [default setting]
Info
0x2550:008
Brake resistor: Warning threshold
50.0 ... [90.0] ... 150.0 %
Warning threshold for brake resistor monitoring.
•
If the utilisation shown in reaches the threshold set, the response
selected in
is effected.
•
The warning is reset with a hysteresis of 20 %.
0x2550:010
Brake resistor: Response to warning
Selection of the response that is executed when the warning threshold
for brake resistor monitoring is reached.
0 No response
1 Fault > CiA402
2 Warning
0x2550:011
Brake resistor: Response to error
Selection of the response to be executed when the error threshold for
brake resistor monitoring is reached.
Associated error code:
•
65282 | 0xFF02 - Brake resistor: overload fault
0 No response
1 Fault > CiA402
2 Warning
18.2
Manual jog parameters
Parameter
Address
Name / setting range / [default setting]
Info
0x2836:001
Manual control mode: Current setpoint
0 ... [30] ... 200 %
Setting of the current setpoint value for manual control.
•
100 % ≡ Rated current ()
0x2836:002
Manual control mode: Frequency
-1000.0 ... [0.0] ... 1000.0 Hz
Setting of the frequency for manual control.
0x2836:003
Manual control mode: Ramp time (current)
0 ... [0] ... 1000 ms
Setting of the period of time during which the current setpoint value is
achieved from zero onwards.
0x2836:004
Manual control mode: Ramp time (frequency)
0 ... [500] ... 10000 ms
Setting of the period of time during which the frequency is achieved
from zero onwards.
The frequency ramp only starts up when the current ramp has reached
the value configured in
0x2836:005
Manual control mode: Time monitoring (frequency)
0 ... [2500] ... 100000 ms
Setting of the time period for time monitoring.
•
The manual control features a time monitoring function which is cou-
pled to a write access to
(Frequency).
•
If no write access to
takes place within the time period
set here, the frequency is moved to zero via the parameterised ramp.
When the 0 Hz have been reached, the inverter changes to the error
status and is inhibited. After acknowledging the error, the CiA402
state machine must be switched from "Switch-on inhibited" back to
the "Operation enabled" state before proceeding with manual con-
trol.
0x2836:006
Manual control mode: Current controller gain
0.00 ... [20.00] ... 750.00 V/A
Setting of the current controller gain.
0x2836:007
Manual control mode: Current controller reset time
0.01 ... [20.00] ... 2000.00 ms
Setting of the current controller reset time.
Additional functions
Manual jog parameters
386
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......