18.3
Mains failure control
Parameter
Address
Name / setting range / [default setting]
Info
0x2D66:001
Mains failure control: Enable function
1 = enable mains failure control.
0 Disabled
2 Enabled
0x2D66:002
Mains failure control: DC-bus activation level
60 ... [75] ... 90 %
Threshold below which the mains failure control is activated if it is ena-
bled (
•
100 % ≡ nominal DC-bus voltage
Recommended setting:
•
In general: 5 ... 10 % above the error threshold for undervoltage (dis-
play in
).
•
230-V devices: 72 %
•
400/480-V devices: 82 %
0x2D66:011
Mains failure control: Filter time
0.00 ... [0.00] ... 60.00 s
0x2D66:012
Mains failure control: Ramp max. torque
0.0 ... [30.0] ... 3276.7 %
0x2D66:013
Mains failure control: Ramp time
0.10 ... [1.00] ... 5.00 s
0x2D66:014
Mains failure control: Actual DC-bus voltage
•
Read only: x.xxx V
Additional functions
Mains failure control
387