Address
Name / setting range / [default setting]
Info
0x2C52:002
Load encoder/master encoder settings (encoder):
Supply voltage
5.0 ... [5.0] ... 12.0 V
•
Setting can only be changed if the inverter is inhibi-
ted.
Setting of the supply voltage.
12.2.3.1
SinCos encoder
The following SinCos encoder types without HIPERFACE® protocol are supported by the inver-
ter:
Type
Increments/revolution
Absolute revolutions
IG1024-5V-V3 (RVS58S)
1024
0
IG2048-5V-S (ITD22)
2048
0
IG2048-5V-S
2048
0
12.2.3.2
SinCos absolute value encoder with HIPERFACE® protocol
The following SinCos encoder types with HIPERFACE® protocol are supported by the inverter:
Type
Increments/revolution
Absolute revolutions
Type code
AM1024-8V-H (SRM50)
1024
4096
(Multiturn)
39
AM1024-8V-H (SFM60)
1024
39
AM1024-8V-K2 (SRM50S)
1024
39
AM128-8V-H (SKM36)
128
55
AM16-8V-H (SEL37)
16
71
AM16-8V-H (SEL52)
16
71
AM512-8V-H (SCM70)
512
7
AS1024-8V-H (SRS50)
1024
4096
(Single-turn)
34
AS1024-8V-K2 (SRS50S)
1024
34
AS16-8V-H (SEK37)
16
66
AS16-8V-H (SEK52)
16
66
AS512-8V-H (SCS70)
512
2
Use of non-supported encoder types
If the type code of the encoder used is not listed in the table of supported encoder types, this
encoder can be introduced to the inverter via two parameters.
In this context, please also observe the information provided in the parameter
description
Parameter
Address
Name / setting range / [default setting]
Info
0x2822:030
Axis commands: Get load encoder/master encoder
information (Hiperface)
Obtain Hiperface information from the encoder for application feedback.
0 Off/Ready
1 On/Start
2 In process
3 Action cancelled
4 No access
5 No access (controller inhibit)
0x2C51:001
Hiperface load encoder/master encoder settings: Type
code detected
•
Read only
Type code read out of the encoder.
This value is "0" if ...
•
a sin/cos encoder is set (
•
a communication error has occurred.
0x2C51:002
Hiperface load encoder/master encoder settings: Type
code manual input
0 ... [0] ... 255
•
Setting can only be changed if the inverter is inhibi-
ted.
Manual setting of the encoder type code (display in
Configuring the feedback system
Second feedback system for the techology application
Encoder settings
218
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......