13.7.3
Asynchronous motor (ASM): Identify Lh saturation characteristic
In case of an asynchronous motor, the relationship between current and torque is basically
determined by the saturation behaviour of the mutual inductance. If the achieved torque
accuracy, especially in the field weakening range should not be sufficient, the accuracy can be
increased by the individual identification of the saturation characteristic. This behaviour can
be measured by the servo inverter.
Conditions for the execution
•
Before this commissioning function is executed, the inverter characteristic and the motor
parameters must be identified
Motor equivalent circuit diagram data
•
The motor may be stalled.
•
The inverter is error-free and in "
" device state.
Response of the motor during "standstill" performance
How to identify the L
h
saturation characteristic:
The identification of the L
h
saturation characteristic can take up to 11 minutes.
1
.
If the servo inverter enabled, disable it .
2
.
Select the drive mode [10] in parameter
: Lh saturation characteristic identification
3
.
Enable the inverter to start the process.
•
Check the progress in 0x2823:002.
•
Disabling the inverter serves to abort the started procedure any time if required.
Already determined characteristic values are rejected in this case.
After successful completion...
...the inverter will be disabled automatically and the points of the determined L
h
saturation
characteristic are set in the parameters
.
•
Save the changed settings.
The »EASY Starter« serves to save the parameter settings of the servo inverter as parame-
ter file (*.gdc).
•
The inverter disable set automatically by the procedure can be deactivated again via the
CiA402 control word
In the event of an error
If an error occurs during the procedure or the pulse inhibit gets active (e.g. due to short-time
undervoltage), the procedure is terminated with inverter disable without the settings being
changed.
Load standard L
h
saturation characteristic
If an incorrect L
h
saturation characteristic has been determined or none at all, it is possible to
load a standard L
h
characteristic.
How to load the standard L
h
saturation characteristic:
1
.
The start is made via the parameter
2
.
For permanent storage: after the process has been completed, save the L
h
saturation char-
acteristic set in .
The »EASY Starter« serves to save the parameter settings of the inverter as parameter file
(*.gdc).
Configuring the motor control
Fine adjustment of the motor model
Asynchronous motor (ASM): Identify Lh saturation characteristic
281
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......