Address
Designation
Default setting
Data type
Factor A
M
Motor utilisation (i²xt) - specific characteristic: y3 =
i03/iN (x3)
100 %
U16
1
-
Motor utilisation (i²xt) - specific characteristic: x4 =
n04/nN (n04 = limit field weakening)
100 %
U16
1
-
Motor utilisation (i²xt) - specific characteristic: y4 =
i04/iN (x4)
100 %
U16
1
-
Motor utilisation (i²xt) - warning threshold
100 %
U16
1
-
Motor utilisation (i²*t)
x % (Read only)
U16
1
X
●
Motor utilisation (i²xt) - monitoring: Error response Fehler > CiA402 [1]
U8
-
Motor utilisation (i²xt) - monitoring: Error threshold 105 %
U16
1
-
Position error/speed error - monitoring: Speed error
- error threshold
50 rpm
U32
1
-
Position error/speed error - monitoring: Speed error
- min. time for error
0 ms
U16
1
-
Position error/speed error - monitoring: Speed error
- error response
No response [0]
U8
-
Position error/speed error - monitoring: Position
error - error threshold
360 °
U32
1
-
Position error/speed error - monitoring: Position
error - min. time for error
0 ms
U16
1
-
Position error/speed error - monitoring: Position
error - error response
No response [0]
U8
-
Mains failure control: Enable function
Disabled [0]
U8
-
Mains failure control: DC-bus activation level
75 %
U8
1
-
Mains failure control: Filter time
0.00 s
U16
100
-
Mains failure control: Ramp max. torque
30.0 %
U16
10
-
Mains failure control: Ramp time
1.00 s
U16
100
-
Mains failure control: Actual DC-bus voltage
x.xxx V (Read only)
U32
1000
X
0x2D81:001
Life-diagnosis: Operating time
x s (Read only)
U32
1
X
0x2D81:002
Life-diagnosis: Power-on time
x s (Read only)
U32
1
X
0x2D81:004
Life-diagnosis: Main switching cycles
- (Read only)
U32
1
X
0x2D81:006
Life-diagnosis: Short-circuit counter
- (Read only)
U32
1
X
0x2D81:007
Life-diagnosis: Earth fault counter
- (Read only)
U32
1
X
0x2D81:009
Life-diagnosis: Fan operating time
x s (Read only)
U32
1
X
0x2D82
Motor actual voltage (Veff)
x.x V (Read only)
U32
10
X
●
0x2D83:001
Motor-Phasenströme: Zero system current
x.xx A (Read only)
I32
100
X
●
0x2D83:002
Motor-Phasenströme: Phase U current
x.xx A (Read only)
I32
100
X
●
0x2D83:003
Motor-Phasenströme: Phase V current
x.xx A (Read only)
I32
100
X
●
0x2D83:004
Motor-Phasenströme: Phase W current
x.xx A (Read only)
I32
100
X
●
Heatsink temperature: Heatsink temperature
x.x °C (Read only)
I16
10
X
Heatsink temperature: Heatsink temperature: Warn-
ing threshold
90.0 °C
I16
10
-
0x2D8A
Actual speed error
x rpm (Read only)
I32
1
X
●
0x2DA2:001
Output power: Effective power
x.xxx kW (Read only)
I32
1000
X
●
0x2DA3:003
Output energy: Warning
0.00 kWh
I32
100
X
0x2DA4:001
Diagnostics of analog input 1: Value in percent
x.x % (Read only)
I16
10
X
Diagnostics of analog input 1: Scaled percent value
x.xx % (Read only)
I16
100
X
●
0x2DA4:016
Diagnostics of analog input 1: Status
- (Read only)
U16
HX ●
0x2DD0:001
Field values: Actual value
x % (Read only)
U16
1
X
●
0x2DD0:002
Field values: Setpoint value
x % (Read only)
U16
1
X
●
0x2DD1:001
Motor currents: Actual D-current (id)
x.xx A (Read only)
I32
100
X
●
0x2DD1:002
Motor currents: Actual Q-current (iq)
x.xx A (Read only)
I32
100
X
●
0x2DD1:003
Motor currents: Setpoint D-current (id)
x.xx A (Read only)
I32
100
X
●
0x2DD1:004
Motor currents: Setpoint Q-current (iq)
x.xx A (Read only)
I32
100
X
●
0x2DD1:005
Motor currents: Motor current (Ieff)
x.xx A (Read only)
I32
100
X
●
* Default setting depending on the size.
Appendix
Parameter attribute list
484
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......