13.9.1.3
UL 508-compliant motor overload monitoring
If the operation of the motor requires the compliance with the UL Standard 508, and the UL
508-compliant motor overload monitoring is realised by the mathematical model of the I²xt
monitoring, the following conditions must be observed.
UL 508 condition 3:
After mains switching and a motor load > 100 %, the I²xt warning must be output faster than
in the same overload case before mains switching.
•
A motor load > 100 % exists if the r.m.s. value of the total motor current displayed in
parameter 0x2DD1:005 is higher than the rated motor current
This condition can be fulfilled by setting the following parameters:
•
Motor utilisation (I²xt): starting value
UL 508 condition 2:
In case of a motor load of 110 %, the I²xt warning at a motor rotating field frequency of 10 Hz
must be output faster than at a motor rotating field frequency of 20 Hz.
•
The current motor rotating field frequency is displayed in parameter 0x2DDD.
•
A motor load of 110 % exists if the r.m.s. value of the total motor current displayed in
parameter 0x2DD1:005 corresponds to 110 % of the rated motor current
.
This condition can be fulfilled by setting the following parameters:
•
I²xt: x1 = n01/nN (n01 ~ 0)
•
I²xt: y1 = i01/iN (x = n01 ~ 0)
•
I²xt: x2 = n02/nN (n02 = reduced cooling limit)
•
I²xt: y2 = i02/iN (x = n02 = reduced cooling limit
UL 508 condition 1:
In case of a motor load of 600 %, the I²xt warning must be output within 20 seconds.
•
A motor load of 600 % exists if the r.m.s. value of the total motor current displayed in
parameter 0x2DD1:005 corresponds to 600% of the rated motor current
This condition can be fulfilled by setting the following parameters:
•
Motor utilisation (I²xt): thermal time constant - laminated core
•
Motor utilisation (I²xt): influence winding
•
Motor utilisation (I²xt): motor overload warning threshold
•
Motor utilisation (I²xt): response
•
Motor utilisation (I²xt): error threshold
Configuring the motor control
Motor protection
Motor overload monitoring (i²*t)
295
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......