Address
Name / setting range / [default setting]
Info
0x5040:111
Status signals limiter
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
Bit 1 SS1 active
Quick stop with subsequent inverter disable is requested.
Bit 2 SS2 active
Quick stop is requested.
Bit 3 SOS active
The "Safe operational stop (SOS)" function is monitored. The "Safe
operational stop (SOS)" function is activated after the "Safe stop (SS2)"
function has been executed.
Bit 4 SLS1 active
Request limited velocity 1. The travel profile changes in accordance with
the parameters set for Limited velocity 1.
Bit 5 SLS2 active
Request limited velocity 2. The travel profile changes in accordance with
the parameters set for Limited velocity 1.
Bit 6 SLS3 active
Request limited velocity 3. The travel profile changes in accordance with
the parameters set for Limited velocity 1.
Bit 7 SLS4 active
Request limited velocity 4. The travel profile changes in accordance with
the parameters set for Limited velocity 1.
Bit 8 SDpos active
Only a positive direction of rotation is permitted.
Bit 9 SDneg active
Only a negative direction of rotation is permitted.
Bit 10 SLI active
The "Safe limited increment (SLI)" function is active.
NOTE: This function is not supported in the technology application!
Bit 11 SSE active
The "Safe stop emergency (SSE)" function is active.
Bit 12 Button S82 active
The "Enable switch (ES)" function for the motion function in special
operation is active.
Note: This function is not supported in the technology application!
Bit 13 Operation modes selector (OMS) active
The "Operation mode selector (OMS)" function was requested for spe-
cial operation.
Note: This function is not supported in the technology application!
Bit 16
Bit 23
0x5040:112
Actual velocity
-214748.3648 ... [0.0000] ... 214748.3647
The current velocity is specified in [units/s]. The velocity is resolved with
4 decimal places.
0x5040:114
Error code
0 ... [0] ... 4294967295
The current error number is displayed.
0x5040:115
Actual torque
-21474836.48 ... [0.00] ... 21474836.47 Nm
The drive-end actual torque is specified in the [Nm]. The torque is speci-
fied with 2 decimal positions.
0x5040:116
Display value 1
0 ... [0] ... 4294967295
The assigned monitor signal is transmitted. Selection takes place via the
Source monitoring 1 parameter.
0x5040:117
Display value 2
0 ... [0] ... 4294967295
The assigned monitor signal is transmitted. Selection takes place via the
Source monitoring 2 parameter.
Configuring the "Sync and Correction" TA
Interface
Status signals
94
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......