Parameter
Address
Name / setting range / [default setting]
Info
0x2D4C:001
Thermisches Modell Motorauslastung (i²xt): Motor
utilisation (i²xt)
1 ... [60] ... 36000 s
Setting of the time constant for the winding.
0x2D4C:002
Thermisches Modell Motorauslastung (i²xt): Thermal
time constant - laminations
1 ... [852] ... 36000 s
Setting of the time constant for the laminated core.
0x2D4C:003
Thermisches Modell Motorauslastung (i²xt): Winding
influence
0 ... [27] ... 100 %
Part of the thermal motor model: distribution factor of the copper wind-
ing influence.
0x2D4C:004
Thermisches Modell Motorauslastung (i²xt): Starting
value
0 ... [0] ... 250 %
Value for initialising the filters for the thermal motor overload monitor-
ing (setting in % of the permissible full load).
Configuring the motor control
Motor protection
Motor overload monitoring (i²*t)
291