Item
Data Plan for the F01S300 Cabinet
Digital parameter ID: 7
Available-level: low level
Name: MDF-door
Digital-alarm-index: 9
NOTE
The digital monitoring parameter of the MDF door status sensor is set here to
monitor the MDF door status. When the door of the MDF compartment is open,
the device reports an alarm. The MDF compartment has the low level when its
door is closed and the device does not report an alarm.
NOTE
The preceding data is configured according to the actual requirements. When the actually planned value
of a parameter is the same as the default value, it is not necessary to configure the parameter.
Example
Assume that the F01S300 cabinet is configured with one 50 AH battery set, the ETP4830 is
configured with 2 rectifier modules, and battery compartment heater and equipment
compartment heater are configured. To configure the environment monitoring parameters of the
ETP4830, do as follows:
huawei(config)#
emu add 1 SMU 0 0 SMU
huawei(config)#
display emu 1
huawei(config)#
interface emu 1
huawei(config-if-smu-1)#
display power system parameter
huawei(config-if-smu-1)#
display power environment parameter
huawei(config-if-smu-1)#
power battery parameter 1 0.15 60 50
huawei(config-if-smu-1)#
power battery temperature 80 -20 80
huawei(config-if-smu-1)#
power battery temperature alarm_upper-limit 50 alarm_lower-
limit -15
huawei(config-if-smu-1)#
power battery-test auto-test permit 120
huawei(config-if-smu-1)#
display power battery-test info 1
huawei(config-if-smu-1)#
power off battery-off-state permit battery-off-voltage 43
huawei(config-if-smu-1)#
power temperature-off battery-off-state permit battery-off-
temperature 53
huawei(config-if-smu-1)#
power environment temperature 68 -20 80 -20
This command is invalid unless in the contition of install the sensor, would
you continue? (y/n)[n]:
y
huawei(config-if-smu-1)#
power environment humidity 80 0 100 0
This command is invalid unless in the contition of install the sensor, would
you continue? (y/n)[n]:
y
huawei(config-if-smu-1)#
power module-num 2 1 2
huawei(config-if-smu-1)#
power outside-digital 2 available-level low-level name
Batt-heater
huawei(config-if-smu-1)#
power outside-digital 3 available-level low-level name
Equip-heater
huawei(config-if-smu-1)#
power outside-digital 4 available-level low-level name SPD
digital-alarm 20
huawei(config-if-smu-1)#
power outside-digital 6 available-level low-level name HEX
digital-alarm 13
huawei(config-if-smu-1)#
power outside-digital 7 available-level low-level name MDF-
door digital-alarm 9
huawei(config-if-smu-1)#
display power system parameter
huawei(config-if-smu-1)#
display power environment parameter
huawei(config-if-smu-1)#
display power alarm
SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide
1 Commissioning
Issue 01 (2014-04-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
114