1.3.16.3 Configuring H801VESC Environment Monitoring Parameters
The MA5608T can monitor the environment status through its built-in virtual environment
monitoring unit (EMU) H801VESC. This topic describes how to configure the H801VESC.
Context
l
The H801VESC is a built-in virtual EMU of the control board on the MA5608T, and the
ALARM port on the control board is connected to the external sensor through an
environment monitoring cable.
l
You need to manually add the H801VESC. The recommended subnode ID is 25.
l
The H801VESC supports seven digital parameters, all of which can be defined by users.
In an F01S200 cabinet, only four digital parameters are used.
l
By default, the valid levels of default digital parameters are all high levels.
Procedure
Step 1
Add the H801VESC.
Run the
emu add
command to add the H801VESC.
Step 2
Query the status of the H801VESC.
Run the
display emu
command to query the status of the H801VESC. Ensure that it is running
properly.
Step 3
Configure the digital parameters.
Run the
interface emu
command to enter the EMU mode.
Run the
vesc digital
command to configure the valid level, name, and alarm ID of the digital
parameters.
Step 4
Query the environment information about the H801VESC.
Run the
display vesc environment info
command to query the environment information about
the H801VESC.
Step 5
Run the
save
command to save the data.
----End
Result
After the configuration, the H801VESC works in the normal state and monitors the digital
parameters set on the MA5608T. When the actual level of a monitored digital parameter is
different from the valid level preset in the system, the MA5608T reports an alarm.
Example
To configure the H801VESC of the MA5608T in an F01S200 cabinet, do as follows (
lists the data plan for configuring the H801VESC of the MA5608T in the F01S200 cabinet):
SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide
1 Commissioning
Issue 01 (2014-04-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
87