limit -15
huawei(config-if-smu-1)#
power battery-test auto-test permit 180
huawei(config-if-smu-1)#
display power battery-test info 1
huawei(config-if-smu-1)#
power off load-off-state forbid load-off-voltage 44
battery-off-state permit battery-off-voltage 43
huawei(config-if-smu-1)#
power temperature-off battery-off-state permit battery-off-
temperature 53
huawei(config-if-smu-1)#
power environment temperature 68 -5 80 -20
This command is invalid unless in the contition of install the sensor, would
you continue? (y/n)[n]:
y
huawei(config-if-smu-1)#
power environment humidity 80 0 100 0
This command is invalid unless in the contition of install the sensor, would
you continue? (y/n)[n]:
y
huawei(config-if-smu-1)#
power module-num 3 1 2 3
huawei(config-if-smu-1)#
power outside-digital 3 available-level low-level name SPD
digital-alarm 20
huawei(config-if-smu-1)#
power outside-digital 5 available-level low-level name HEX
digital-alarm 13
huawei(config-if-smu-1)#
power outside-digital 6 available-level low-level name MDF-
door digital-alarm 9
huawei(config-if-smu-1)#
display power system parameter
huawei(config-if-smu-1)#
display power environment parameter
huawei(config-if-smu-1)#
display power alarm
huawei(config-if-smu-1)#
quit
huawei(config)#
save
1.3.16.9 Configuring the Power3000 Environment Monitoring Mode
This topic describes how to configure environment monitoring parameters by using the CLI.
Configuration Process
The monitoring parameters can be reported to the control system only when the data for the
Power3000 is configured correctly in the system.
lists the commands used during the configuration.
Table 1-38
Commands for configuring the Power3000
To...
Run the Command...
Add an EMU
emu add
Query the configuration
parameters of the power system
display power system parameter
Query the power environment
parameters
display power environment parameter
Configure the battery charging
parameters
power charge
Configure the battery
management parameters
power battery parameter
Configure the upper/lower
temperature alarm limits or the
upper/lower temperature test
limits
power battery temperature
SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide