Item
Data Plan
Environment monitoring
parameters
Upper alarm threshold of the temperature: 68°C
Lower alarm threshold of the temperature: -5°C
Upper test threshold of the humidity: 80°C
Lower test threshold of the humidity: -20°C
External extended digital
parameters
Digital parameter ID: 0-6
This digital parameter is set according to the actual requirements.
NOTE
The preceding data is configured according to the actual requirements. When the actually planned value
of a parameter is the same as the default value, it is not necessary to configure the parameter.
Configuration Example
The following considers the configuration plan of the Power3000 as an example to describe the
process of configuring the environment monitoring parameters of the Power3000.
huawei(config)#
emu add 0 POWER3000 0 0 POWER3000
huawei(config)#
display emu 0
huawei(config)#
interface emu 0
huawei(config-if-power3000-0)#
display power system parameter
huawei(config-if-power3000-0)#
display power environment parameter
huawei(config-if-power3000-0)#
power battery parameter 1 0.15 60 65
huawei(config-if-power3000-0)#
power battery-test auto-test permit 60
huawei(config-if-power3000-0)#
power temperature-off battery-off-state permit
battery-off-temperature 53
huawei(config-if-power3000-0)#
power environment temperature 68 -5 80 -20
huawei(config-if-power3000-0)#
display power system parameter
huawei(config-if-power3000-0)#
display power environment parameter
huawei(config-if-power3000-0)#
quit
huawei(config)#
save
1.3.16.10 Commissioning the EMU_TCU
This topic describes how to commission the TCU to ensure that it monitors and controls the
temperature conditions of the heat exchanger according to the actual conditions.
Context
NOTE
Commissioning the TCU only when the device is installed in the outdoor cabinet scenario.
The TCU is used to monitor the running status of the heat exchanger and to set the heating start
temperature or the heating stop temperature according to actual conditions to ensure the normal
heat dissipation of the device.
When commissioning the TCU, pay attention to the following points:
l
The TCU sub-nodes are numbered from 0 to 31.
l
When the system is configured with multiple EMUs simultaneously, make sure that the
sub-nodes do not conflict with each other.