To...
Run the Command...
Configure the power distribution
parameters
power supply-parameter
Configure the battery
discharging test parameters
power battery-test
Configure the parameters for the
power rectifier module
power module-num
Configure the environment
monitoring parameters
power environment
Configure the load and battery
high-temperature power-off
parameters
power temperature-off
Configure the external extended
digital parameters
power outside-digital
1.
Log in to the device through the maintenance terminal and add an EMU.
2.
Query the status of the GEPS4845.
3.
Enter the environment monitoring configuration mode and query the default configuration.
4.
Configure the battery management parameters.
5.
Configure the battery discharging test parameters.
6.
Configure the environment parameters.
7.
Configure the load and battery high-temperature power-off parameters.
8.
Configure the extended digital parameters.
9.
Query the information about the configured parameters and environment parameters of the
power system.
10. Query the alarms, and confirm that the door status alarm other than alarms for other
monitoring parameters is generated. The door status sensors of the device compartment
and the temperature control compartment are in serial connection, and are monitored as a
variable.
11. Save the data.
12. Close all doors of the cabinet. Then, query the alarm information again, and confirm that
there is no alarm for any monitoring parameter.
Data Plan
In this topic, the application in the F01D500 cabinet is considered as an example.
provides the data plan for configuring the monitoring parameters of the GEPS4845.
SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide
1 Commissioning