Item
Data Plan for the F01S300 Cabinet
External extended
digital parameters
Digital parameter ID: 2
Available-level: low level
Name: Batt-heater
NOTE
The monitoring digital parameter of the battery compartment heater (optional
configuration) is set here to monitor the battery compartment heater. When the
battery compartment heater is faulty, the device reports an alarm. The battery
compartment heater has the low level when working properly and the device
does not report an alarm.
Digital parameter ID: 3
Available-level: low level
Name: Eqiup-heater
NOTE
The monitoring digital parameter of the equipment compartment heater
(optional configuration) is set here to monitor the equipment compartment
heater. When the equipment compartment heater is faulty, the device reports an
alarm. The equipment compartment heater has the low level when working
properly and the device does not report an alarm.
Digital parameter ID: 4
Available-level: low level
Name: SPD
Digital-alarm-index: 20
NOTE
The monitoring digital parameter of the surge protector is set here to monitor
the surge protector. When the surge protector is faulty, the device reports an
alarm. The surge protector has the low level when working properly and the
device does not report an alarm.
Digital parameter ID: 6
Available-level: low level
Name: HEX
Digital-alarm-index: 13
NOTE
The monitoring digital parameter of the heat exchanger is set here to monitor
the status of the heat exchanger. When the heat exchanger is faulty, the device
reports an alarm. The heat exchanger has the low level when working properly
and the device does not report an alarm.