Example
To add a TCU (emuid: 2; sub-node: 7), and set the heating start temperature to -10°C and the
heating stop temperature to 30°C for heat exchanger 2, do as follows:
huawei(config)#
emu add 2 TCU 0 7 tcu
huawei(config)#
interface emu 2
huawei(config-if-tcu-2)#
tcu heat temperature
{ start-temperature<F><-90,40> }:
-10
{ end-temperature<F><-90,40> }:
30
Command:
tcu heat temperature -10 30
Send command to environment monitor board ,please wait for a moment
huawei(config-if-tcu-2)#
Execute command successful
1.3.16.11 Commissioning the EMU_FAN
This topic describes how to commission the FAN to ensure that it monitors the environmental
conditions of the fans of the device according to the actual conditions.
Context
NOTE
When the device is delivered, the EMU_FAN is correctly connected to the shelf. The connection need not
be changed for the device commissioning. In certain cases, if the EMU needs to be configured in other
shelves, reconnect the EMU. For details, see this topic.
The FAN is used to monitor the running status of the fans and to set the fan rotation speed
according to actual conditions to ensure the normal heat dissipation of the device.
When commissioning the FAN, pay attention to the following points:
l
The EMU sub-nodes are numbered from 0 to 31.
l
When the system is configured with multiple EMUs simultaneously, make sure that the
sub-nodes do not conflict with each other.
l
It is recommended that you use the
auto
mode as the fan speed adjustment mode.
lists the default configuration of the FAN.
Table 1-41
Default configuration of the FAN
Parameter
Default Value
Sub-node
1
Fan speed
adjustment mode
Automatic
Whether to report
the fan alarm
Permit
SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide