Item
Data Plan for the F01D500 Cabinet
Environment monitoring
parameters
Upper alarm threshold of the temperature: 68°C
Lower alarm threshold of the temperature: -5°C
Upper test threshold of the humidity: 80°C
Lower test threshold of the humidity: -20°C
Load and battery high-
temperature power-off
parameters
Load high-temperature power-off permission status: forbid
Battery high-temperature power-off permission status: permit
Temperature for load high-temperature power-off: 70°C
Temperature for battery high-temperature power-off: 53°C
External extended digital
parameters
Digital parameter ID: 0
This digital parameter is set according to the actual requirements.
The monitoring digital parameter of the external fan tray is set
here to monitor the fan tray. When the fan tray is faulty, the host
reports an alarm.
Valid level of digital parameter 0: low level
When the low level represents the valid level, the host does not
report an alarm in the case of low level.
Digital parameter ID: 1
This digital parameter is set according to the actual requirements.
The monitoring digital parameter of the external fan tray is set
here to monitor the fan tray. When the fan tray is faulty, the host
reports an alarm.
Valid level of digital parameter 1: low level
When the low level represents the valid level, the host does not
report an alarm in the case of low level.
Digital parameter ID: 2
This digital parameter is set according to the actual requirements.
Valid level of digital parameter 2: low level
When the low level represents the valid level, the host does not
report an alarm in the case of low level.
Digital parameter ID: 3
This digital parameter is set according to the actual requirements.
The monitoring digital parameter of the surge protector is set here
to monitor the status of the surge protector. When the surge
protector is faulty, the host reports an alarm.
Valid level of digital parameter 3: low level
When the low level represents the valid level, the host does not
report an alarm in the case of low level.