Table 1-33
Data plan for configuring the monitoring parameters of the GEPS4845
Item
Data Plan for the F01D500 Cabinet
EMU
Type: POWER4845
SN: 0
Subnode ID: 0
The subnode ID must be the same as the subnode setting of the
corresponding DIP switches on the EMU, but the subnode ID
must be different from IDs of the other subnodes on the same
bus.
Charging parameters of
the battery
Charging mode of the battery: automatic
Equalized charging voltage of the battery: 56.5 V
Float charging voltage of the battery: 53.5 V
Battery management
parameters
Current-limiting coefficient for battery charging: 0.15
Interval of battery equalized charging: 60 days
Number of battery sets: 1
Capacity of the battery set: 150 AH
The battery capacity is configured according to the actual value.
the F01D500 cabinet uses the 2 * 75 AH or 2 * 92 AH batteries.
The upper/lower
temperature alarm limits
or the upper/lower
temperature test limits
Upper temperature threshold of the battery set: 60°C
Lower temperature threshold of the battery set: -40°C
Temperature compensation coefficient of the battery set: 100 mV
Power supply load power-
off and battery set power-
off parameters
Load power-off permission status: forbid
Battery set power-off permission status: permit
Load power-off voltage: 44 V
Battery set power-off voltage: 43 V
Power distribution
parameters
AC overvoltage alarm threshold of the power supply: 280 V
AC undervoltage alarm threshold of the power supply: 180 V
DC overvoltage alarm threshold of the power supply: 58 V
DC undervoltage alarm threshold of the power supply: 45 V
Battery discharging test
parameters
Battery auto-discharging test: auto-test
Battery set auto-discharging test permission status: permit
Battery auto-discharging test period: 60d
Power rectifier module
parameters
The number of the power rectifier modules: 0
The number of the power rectifier modules is configured
according to the actual value. GEPS4845 supports up to 3
rectifier modules.
SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide
1 Commissioning
Issue 01 (2014-04-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
106