Indicators
Table 3-61 ETH converter indicators
Indicator Color
Name
Status
Description
PWR
Green Power input
status
indicator
Steady on
The power input is normal.
Off
There is no power input.
RUN
Green Operating
status
indicator
Off
The power supply is
abnormal.
Blinking at
long
intervals
The ETH converter
successfully registers with
the ECC800-Pro and the
software runs properly (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
Blinking at
short
intervals
The communication fails or
the ETH converter fails to
register with the ECC800-Pro
(the indicator blinks at 4 Hz,
on for 0.125s and then off
for 0.125s).
Blinking
The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 10s.
ALM
Red
Alarm
indicator
Steady on
A system failure alarm is
generated.
Off
No system alarm is
generated.
3.2.18 PAD
The pad allows the wireless access from the data center management system. You
can monitor the equipment in the data center and environmental parameters in
real time over the app. The recommended model is T5-10.
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
3 Device Description
Issue 02 (2020-09-07)
Copyright © Huawei Technologies Co., Ltd.
68