Procedure
Step 1 Set parameters for a door status sensor.
NO TE
In this example, the door status sensor is connected to the AI/DI_1 port on the independent
deployment AI_DI 1.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Choose System Settings > Signal Name Modify. The Batch Signal
Configuration page is displayed.
3. Set Device Type to Independent Deployment AI_DI Unit, set Device Name
to Independent Deployment AI_DI1 Unit, and click OK.
4. On the query result tab page, set the new signal name of AI/DI_1 to Door1
and click Submit.
NO TE
Order number of door sensor name is same as cabinet.
5. Choose Monitoring > System > Independent Deployment AI_DI Unit Group
> Independent Deployment AI_DI1 Unit > Running Parameters > AI/DI_1
Port Settings.
6. Set Door1 sensor to Enable and click Submit.
7. Set Door1 sensor type to Door sensor, ensure that Door1 power supply is
Yes, and click Submit.
8. Perform the preceding operations to set parameters for ports AI/DI_2 to AI/
DI_8.
Step 2 Check the door status sensor functions.
Table 6-4 Function check
Check Method
Normal Connection Status
Open the cabinet door.
Door1 DI alarm is generated on the active
alarm page of the app or WebUI.
----End
6.4.1.2 Commissioning a Door Status Sensor (Connected to the AI/DI Port on
the Rack Environment Unit)
If a door status sensor is installed, perform the following steps to configure it.
Context
●
If the sensor is prefabricated, only check its settings.
●
If multiple door status sensors are connected, commission one door status
sensor first and then commission the other door status sensors in the same
way.