If the connection fails, check whether the device is properly connected to
the ECC800-Pro, whether the device and ECC800-Pro are running
properly, and whether the parameter settings are consistent with the
device parameters.
5. Connect the electronic locks of other cabinets.
Step 5 Commission the cabinet electronic clasp locks.
Table 5-16 Function check
Function
Path
Setting
View
cabinet
electronic
clasp lock
informatio
n
Choose
Monitorin
g >
Cabinet >
IT
Cabinet10
1> E-
LOCK1
.a
Click the Running
Info tab.
View the running information
about cabinet electronic clasp
lock 1 on the WebUI.
Change a
cabinet
electronic
clasp lock
name
Click the Running
Parameters tab.
Change the cabinet electronic
clasp lock name.
Remotely
open a
cabinet
electronic
clasp lock
Click the Controls
tab.
Select Open front door or Open
back door from the Cabinet
door control drop-down list box,
and click Submit to remotely
open the door.
Open
cabinet
electronic
clasp locks
in batches
Choose Monitoring > Cabinet,
click the Controls tab
Select Open front door, Open
back door, or Open all doors
from the Open the door drop-
down list box, select the setting,
and click Submit. The cabinet
electronic clasp locks unlock the
doors in batches based on the
signal value.
a: Intelligent lock 1 of IT cabinet 101 is used as an example.
----End
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
5 Power-On Commissioning
Issue 02 (2020-09-07)
Copyright © Huawei Technologies Co., Ltd.
125