NO TE
Click Link high temperature with skylight open on the Linkage Group tab page. If it is in on
state, the corresponding logic configurations on the Linkage Logic List tab page are available. If
it is in off state, the corresponding logic configurations on the Linkage Logic List tab page are
unavailable.
----End
Follow-up Procedure
After the alarm has been cleared when high temperature linkage occurs, perform
the following operations: Close the skylights manually.
6.6.1.3 (Optional) Commissioning an Intelligent Aisle Light
Prerequisites
The upstream power input circuit breaker of the AC actuator is turned on.
Context
After the intelligent aisle lighting is set successfully, perform the following steps:
●
After the door is opened using the access control system, the lighting is
turned on.
NO TE
An access control system is involved in the scenario.
●
In the smart module aisle, the lighting is turned on when a camera and a
multi-functional sensor detect that someone enters.
●
The lighting is turned off when the camera and the multi-functional sensor
fail to detect any person in the aisle within 10 minutes.
NO TE
When using the intelligent lighting function, pay attention to the following:
● If a foreign object is hung on the skylight ceiling of the smart module and when the foreign
object moves, the camera may mistakenly generate a motion detection alarm to change the
lighting status.
● When the human body moves, the camera generates a motion detection alarm and the
lighting is turned on. If the motion amplitude of the human body is small, the camera
cannot generate the motion detection alarm. If the lighting is turned off due to this reason,
wave to the camera and the lighting is turned on again.
● If light greatly changes outside the smart module, the camera may mistakenly generate a
motion detection alarm and the lighting is mistakenly turned on.
● If you manually turn off the lighting when you leave the smart module, the lighting may be
turned on again when the camera detects that the person leaves.
● The effective detection distance of the multi-functional sensor is 2.5 m.
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
6 Feature Description
Issue 02 (2020-09-07)
Copyright © Huawei Technologies Co., Ltd.