Table 3-69 T/H sensor specifications
Item
Specifications
Temperature measuring range
–20°C to +80°C
Temperature accuracy
±0.5°C (25°C)
≤ ±1°C (full measuring range)
Operating temperature
–20°C to +80°C
Operating voltage
9–16 V DC
Storage temperature
–40°C to +80°C
Output
Two RJ45 ports, bidirectional cascading
3.2.19.4 T/H Sensor (BOM Number: 02311FQG)
Figure 3-42 Appearance
(1) RS485-OUT
(2) RS485-IN
(3) DIP switch
(4) Button
(5) NTC1–3
(6) NTC4–6
(7) Display
Table 3-70 T/H sensor specifications
Item
Temperature
Humidity
Measurement range
–40°C to +70°C
0%–100% RH
Measurement precision
≤±1°C (–20°C to
+60°C)
≤±5% RH (25°C, 20%–80%
RH)
Extended temperature
collection port
Provides two RJ45 ports to connect to six NTC
temperature sensors, each RJ45 port connecting to
three NTC temperature sensors.
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
3 Device Description
Issue 02 (2020-09-07)
Copyright © Huawei Technologies Co., Ltd.
74