5. Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_3
Port Settings.
6. Set Door1 sensor to Enable, set Door1 sensor type to Door sensor, and click
Submit.
Step 2 If the number of cabinets is less than or equal to 2, set the door status sensor
parameters.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Choose System Settings > Signal Name Modify. The Batch Signal
Configuration page is displayed.
3. Set Device type to ECC800 and Device name to ECC800, and click OK.
4. On the query result tab page, set the new signal name of AI/DI_3 to Door1
and click Submit. Change the new signal name of AI/DI_5 to Door2 and click
Submit.
5. Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_3
Port Settings.
6. Set Door1 sensor to Enable, set Door1 sensor type to Door sensor, and click
Submit.
7. Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_5
Port Settings.
8. Set Door2 sensor to Enable, set Door2 sensor type to Door sensor, and click
Submit.
Step 3 If there are more than two cabinets, set the door status sensor parameters.
1. Set door status sensor parameters for the IT cabinet by referring to step 1.
2. Choose System Settings > Signal Name Modify. The Batch Signal
Configuration page is displayed.
3. Set Device Type to UIM, set Device Name to UIM, and click OK.
4. On the query result tab page, set the new signal name of AI/DI_1 to Door2
and click Submit.
NO TE
Order number of door sensor name is same as that of the cabinet.
5. Choose Monitoring > System > UIM Group > UIM1 > Running Parameters
> AI/DI_1 Port Settings.
6. Set Door2 sensor to Enable and click Submit.
7. Set Door2 sensor type to Door sensor, ensure that Door2 power supply is
set to Yes, and click Submit.
8. Perform the preceding operations to set parameters for ports AI/DI_2 to AI/
DI_8.