Table 6-55 Information obtained from the NMS
Item
Default
Value
Description
SNMP version
SNMPv3
SNMP version and port number used by the
ECC800-Pro and NMS. The SNMP versions
include SNMPv1, SNMPv2c, and SNMPv3.
SNMP port number 161
● Read community
name
● Write
community
name
-
If you use SNMPv1 or SNMPv2c, enter the
read and write community names that comply
with the NMS. Otherwise, the ECC800-Pro will
not connect to the NMS. The read community
name must be different from the write
community name.
● User name
● MD5/SHA
password
● DES/AES
password
-
To enhance the security, you need a user
name and password for authentication if you
use SNMPv3. After the authentication
succeeds, the ECC800-Pro can communicate
with the NMS.
Trap target address
-
IP address of the NMS server.
Trap port
162
Port defined by the user.
Context
●
SNMPv3 parameters should be set before connecting the ECC800-Pro to the
NMS. These parameters are required for setting up the ECC800-Pro on the
NMS.
●
SNMPv1 and SNMPv2c are insecure. Therefore, SNMPv3 is recommended.
This section uses SNMPv3 as an example.
Procedure
Step 1 Apply to the equipment room network administrator for a fixed IP address.
Step 2 Set the IP address, subnet mask, and default gateway on the ECC800-Pro WebUI.
Table 6-56 IP parameters
Path
Parameter Default
Value
Setting
System
Settings >
System
Parameter
s >
Monitor IP
> WAN_1
IP
192.168.8.1
0
Set this parameter based on the IP
address assigned by the network
administrator.
Subnet
mask
255.255.25
5.0
Set this parameter based on the
subnet mask assigned by the network
administrator.
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
6 Feature Description
Issue 02 (2020-09-07)
Copyright © Huawei Technologies Co., Ltd.
242