NO TE
– The 17:00:00 data includes the data from 17:00:00 to 18:00:00.
– If the query time is between 18:00:00 and 19:00:00 and the time has not arrived at
19:00:00 yet, then the displayed time is 18:00:00 and the data includes the data
from 18:00:00 to the query time.
Figure 6-68 Viewing historical PUE data
----End
6.9 Battery Management
If iBOXs and iBATs are configured, perform the following steps to commission
them.
6.9.1 Setting iBOX and iBAT Parameters
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose Monitoring > Power Distribution > iBOX > Running Parameters.
Step 3 Click Unhide All Advanced Signals, set iBOX single battery qty., Batt.
installation time, Single battery capacity, Current source, and Battery string
No.. Retain default values for other parameters.
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
6 Feature Description