UUT Calibration Setup
UUT Connection Test
4
4-17
5.
Plot voltage and current for
Phases A, B
, and
C
. Plot
TVE, Phase Error
,
Magnitude Error, Frequency Error
and
ROCOF Error
as shown on the Plot
Configuration Dialog shown below.
gtu150.png
Figure 4-7. Plot
6.
Look at the plots for both voltage and current. Check the Magnitude Error and Phase
Error plots to make sure all UUT phases are connected correctly to the 6135A.
Note
Common issues are incorrect phase order in the PMU Personality or
incorrectly connected voltage or current phase inputs. Look for 120 degree
or 180 degree phase errors indicating swapped phase order or reversed
red/black input connections.