Introduction and Specifications
General Specifications
1
1-21
General Specifications
Input Power
Voltage
................................................................... 100 V to 240 V with up to ±10 % fluctuations
Frequency
.............................................................. 47 Hz to 63 Hz
Maximum consumption
........................................ 3,500 VA Max
Dimensions
Size
Height.................................................................. 1,170 mm (46 in)
Width ................................................................... 600 mm (24 in)
Depth .................................................................. 800 mm (32 in)
Weight
.................................................................... 170 kg (374 lb)
Weight in shipment crate
..................................... 210 kg (462 lb)
Environment
Warm-Up Time
....................................................... 1 hour
Temperature and Performance
Operating ............................................................ 5 °C to 35 °C
Storage ............................................................... 0 °C to 50 °C
Transit temperature range ................................. 0 °C to 50 °C. Transit outside this temperature range (-20 °C to 0 °C,
or 50 °C to 60 °C) must be limited to <100 hours
Relative
Humidity
Operating ............................................................ <80 % 5 °C to 30 °C ramping down linearly to 50 % at 35 °C
Storage ............................................................... <95 %, non-condensing 0 °C to 50 °C
Operating Altitude
................................................. 0 m to 2,000 m
Storage Altitude
.................................................... 0 m to 12,000 m
Standard and Agency Approvals
Safety
..................................................................... Complies with IEC 61010-1, Overvoltage Category II, Pollution degree
2
EMI/RFI/EMC
.......................................................... IEC 61326-1: Controlled EM Environments, FCC part 15 sub-part B
class A
Electrical Source Accuracy Specifications
See specifications in the 6100B/6105A Users Manual.
Performance Specifications for IEEE C37.118.1a-2014 Tests
Parameter
TVE (%)
FE (Hz)
RFE (Hz/s)
Steady State
0.1
0.0005
0.001
Dynamic, Modulation
0.3
0.001
0.02
Dynamic, Ramp
0.1
0.0005
0.01
Parameter
Delay Time (s)
Step Time Accuracy
0.0002
Measurement reporting latency test accuracy (s)
0.00005
THD of fundamental (% of setting)
0.02
Содержание 6135A/PMU
Страница 28: ...6135A PMU Operators Manual 2 2...
Страница 44: ...6135A PMU Operators Manual 3 2...
Страница 70: ...6135A PMU Operators Manual 3 28...
Страница 72: ...6135A PMU Operators Manual 4 2...
Страница 92: ...6135A PMU Operators Manual 4 22 gtu135 jpg Figure 4 12 Problem All Outputs Forced Off...
Страница 94: ...6135A PMU Operators Manual 5 2...
Страница 102: ...6135A PMU Operators Manual 5 10...
Страница 104: ...6135A PMU Operators Manual 6 2...
Страница 120: ...6135A PMU Operators Manual 7 2...
Страница 138: ...6135A PMU Operators Manual 7 20 gtu120 emf Figure 7 18 Example Report...
Страница 140: ...6135A PMU Operators Manual 8 2...
Страница 150: ...6135A PMU Operators Manual 9 2...
Страница 160: ...6135A PMU Operators Manual A 4...